PG Thread vs Metric Thread Cable Glands: What's the Difference?

November 11, 2026

Share:

PG and metric cable glands use different thread geometries, naming systems, and dimensional standards, so they are not directly interchangeable. Metric glands are normally selected for new equipment, while PG glands remain useful for legacy European machinery, older electrical enclosures, and retrofit work where the existing hole is already threaded for PG.

!

In this guide, I explain the PG thread vs metric thread cable glands difference, show why similar-looking sizes such as PG13.5 and M20 should not be substituted automatically, and provide a field-identification and purchasing method. I also include practical information for electrical enclosures, industrial control panels, waterproof cable entries, and mixed equipment fleets.

Key Takeaways

  • PG threads use a legacy Panzergewinde system, while metric glands use M-designated diameter and pitch values.
  • PG and metric cable glands can look similar but differ in pitch, profile, diameter, and mating compatibility.
  • A gland must match both the enclosure thread and the cable’s actual outer diameter and sealing range.
  • Metric glands are generally preferred for new equipment, while PG remains practical for legacy European installations.
  • Cross-threading can damage the enclosure, reduce clamping force, and invalidate the intended IP protection.

PG Thread vs Metric Thread Cable Glands: Key Differences

The main difference is the thread standard used to connect the gland to an enclosure. PG cable glands use Panzergewinde threads that were commonly specified for older European electrical equipment and are identified by designations such as PG7, PG9, PG11, and PG13.5. Metric cable glands use an M designation followed by the nominal thread diameter, such as M16, M20, or M25, with pitch normally shown separately.

Both designs generally use straight external threads rather than tapered pipe threads. However, the thread flank profile, pitch, nominal diameter, and size notation are different. PG sizes are not simply measurements in millimeters, so a PG13.5 gland should not be treated as a 13.5 mm metric gland.

Feature PG cable gland Metric cable gland
Thread designation PG7, PG9, PG11, PG13.5, PG16 M12, M16, M20, M25, M32
Naming basis Legacy PG size system Nominal outside diameter in millimeters
Typical thread profile Panzergewinde profile, commonly associated with an 80° thread angle ISO metric profile, commonly based on a 60° thread angle
Pitch notation Built into the PG size specification Stated in millimeters, such as M20 × 1.5
Typical application Older European machinery and replacement work New electrical equipment and current enclosure designs
Direct interchangeability Not compatible with metric holes Not compatible with PG holes
Main selection factors Existing hole, cable diameter, sealing range, material, IP rating Existing hole, cable diameter, pitch, material, IP rating

The practical result is simple: the gland thread must match the enclosure thread exactly enough to provide full engagement and stable compression. A similar outside diameter does not establish compatibility because a mismatch can occur in pitch, flank angle, crest diameter, or thread depth.

What Are PG Cable Glands?

PG cable glands use the older Panzergewinde thread system, which was widely used in European electrical equipment. The designation identifies a position in the PG size series rather than directly stating the gland’s thread diameter. For example, PG13.5 commonly has a thread outside diameter close to 20.4 mm, which is one reason it is frequently compared with M20.

A PG Type cable connector normally combines an external threaded body, a sealing insert, a compression nut, and sometimes a locknut or sealing washer. When the compression nut is tightened, the sealing insert contracts around the cable jacket and provides strain relief. The thread connects the gland to the enclosure, while the internal insert controls cable clamping and environmental sealing.

PG glands are still encountered in older control cabinets, motors, sensors, junction boxes, machinery imported from Europe, and replacement projects. I recommend confirming the existing thread before ordering replacements because the label on the original gland may be missing, damaged, or difficult to read after years of service.

What Are Metric Cable Glands?

Metric cable glands use an M designation based on the nominal thread diameter. Common examples include M12 × 1.5, M16 × 1.5, M20 × 1.5, M25 × 1.5, and M32 × 1.5, although other pitches and special versions are available. The product designation should include both the diameter and pitch whenever the enclosure specification requires precise identification.

Metric glands operate through the same general mechanical principle as PG glands. The body is installed through a threaded enclosure hole, the cable passes through the gland, and the compression nut deforms an elastomer seal around the cable jacket. The correct gland is determined by matching the enclosure thread with the cable’s measured outer diameter and the gland’s published sealing range.

For new electrical equipment, I normally specify metric cable glands unless the machine standard, customer drawing, or regional requirement calls for another system. Metric threads simplify documentation because the designation communicates the nominal diameter and pitch directly, which helps procurement and maintenance teams reduce identification errors.

Are PG and Metric Cable Glands Interchangeable?

PG and metric cable glands are not directly interchangeable. A PG gland should not be forced into a metric threaded hole, and a metric gland should not be forced into a PG threaded hole, even when the outside diameters appear close. The mismatch can produce cross-threading, incomplete engagement, an uneven sealing face, or damage to the enclosure hole.

The most common misconception involves PG13.5 and M20. Their nominal outside dimensions may appear similar, but their thread systems are different, so a PG13.5 gland is not a direct replacement for an M20 gland. The reverse is also true: an M20 gland should not be installed in a PG13.5 hole without a properly engineered conversion method.

Existing enclosure thread Commonly considered replacement Direct substitution? Correct approach
PG7 M12 No Confirm dimensions and use a suitable adapter or rework the hole
PG9 M16 No Verify thread profile, hole condition, and cable range before conversion
PG11 M20 No Use the original PG size or an approved conversion component
PG13.5 M20 No Do not rely on similar diameter; confirm pitch and profile
PG16 M25 No Match the enclosure thread or replace the entry component
M20 × 1.5 PG13.5 No Use an M20 gland or an engineered adapter with sealing provisions

Thread compatibility and cable clamping range are separate checks. A gland may have the correct cable sealing range but the wrong enclosure thread, or it may fit the enclosure while failing to clamp the cable securely. I treat both conditions as mandatory acceptance criteria.

How to Identify a PG or Metric Cable Gland

I use a field-identification workflow that combines markings, measurements, and documentation rather than relying on appearance alone. This is especially important when a stainless steel or nickel-plated brass gland has been installed in a crowded control panel and the original packaging is unavailable.

Check the marking and equipment documentation

First, inspect the gland body, compression nut, locknut, and enclosure drawing for markings such as PG9, PG13.5, M20, or M20 × 1.5. Look for the electrical enclosure bill of materials, replacement-parts list, machine manual, or manufacturer drawing because these records may identify the thread even when the gland itself is unmarked.

Sager, identified on its company information pages as Wenzhou Sager Electric Co., Ltd., supplies electrical wiring devices and customized electrical products. When sourcing a replacement from any supplier, I compare the product designation with the enclosure drawing rather than selecting a gland only from a photograph or a similar-looking catalog image.

Measure the outside diameter with calipers

Remove the gland only after isolating the equipment and confirming that the cable can be supported safely. Measure the external thread’s major diameter with calipers, taking care not to measure across the compression nut or a damaged section. Record the result in millimeters and compare it with the manufacturer’s dimensional table.

Diameter alone is not enough because different thread systems can have close nominal values. For example, a PG13.5 thread can be close in diameter to an M20 thread, yet the two may still differ in thread angle and pitch. I use the diameter measurement as a screening step, not as final proof.

Measure pitch with a thread-pitch gauge

Use a metric pitch gauge to test metric candidates such as 1.0 mm, 1.5 mm, or 2.0 mm. For PG candidates, use the relevant PG or unified thread gauge where available, or compare the measured pitch and profile with the gland manufacturer’s dimensional data.

A pitch gauge should sit fully in the thread valleys without rocking or leaving visible gaps. If the gauge does not match cleanly, I stop the identification process rather than forcing a gland into the hole. A damaged first thread can create a false reading, so measurements should be taken on an undamaged section or verified against the enclosure’s original documentation.

Inspect the thread profile and hole condition

Metric and PG threads can differ in flank angle and crest form, so profile inspection helps resolve cases where diameter and pitch measurements are inconclusive. A magnifying glass, thread comparator, or optical measurement system can reveal whether the thread is worn, flattened, plated, or contaminated with sealant.

I also inspect the hole for burrs, cross-threading, paint buildup, corrosion, and insufficient thread depth. Even the correct gland may fail to seal if the enclosure face is uneven or if the gland cannot achieve the specified engagement length and compression.

Cable Gland Size Selection by Cable Diameter

After identifying the enclosure thread, I select the gland based on the cable’s actual outside diameter. The cable diameter should be measured over the finished jacket, including any irregularity that will pass through the sealing insert. I then compare that value with the gland’s minimum and maximum sealing range rather than using the cable conductor size alone.

Selection factor What I verify Why it matters
Enclosure thread PG or metric designation, diameter, pitch, profile Prevents cross-threading and incorrect engagement
Cable outer diameter Measured jacket diameter in millimeters Determines whether the seal can compress correctly
Sealing range Manufacturer’s minimum and maximum cable diameter Confirms clamping and environmental protection
Gland material Nylon, brass, nickel-plated brass, stainless steel Affects corrosion resistance, mechanical strength, and chemical compatibility
IP rating Required IP level, such as IP54, IP65, or IP68 Confirms suitability for dust and water exposure when installed correctly
Locknut and washer Thread-matched accessories and enclosure face seal Supports secure mounting and prevents water paths
Certification Product, material, temperature, and application approvals Required for regulated, hazardous, marine, or industrial installations

A stated IP68 rating applies only when the gland, cable, enclosure interface, and installation method meet the relevant test conditions. I do not assume that an IP68 gland automatically creates an IP68 enclosure if the locknut, washer, hole, cable diameter, or tightening procedure is incorrect.

Choosing PG or Metric for New and Existing Equipment

For new equipment, metric is usually the more practical choice when the project documentation is based on current metric mechanical standards. Metric designations are easier to communicate across engineering, purchasing, and maintenance teams because the nominal diameter and pitch are explicit. I also prefer one consistent thread system across a new panel or machine unless the customer specification requires PG, NPT, or another standard.

For legacy European equipment, PG can remain the correct choice because the existing enclosure hole determines the replacement thread. Replacing the complete enclosure entry with a metric threaded component may require drilling, tapping, repainting, clearance checks, and a new sealing assessment. In a retrofit, retaining PG can reduce mechanical changes and preserve the original cable-entry arrangement.

When a facility operates mixed PG, metric, and NPT equipment, I recommend creating separate spare-parts groups. Each group should identify the thread standard, size, cable sealing range, material, IP rating, and approved supplier part numbers. I also label the storage bins and maintenance drawings so that a visually similar M20 gland is not issued for a PG13.5 repair.

Procurement and Installation Checklist

Before placing an order, I verify the following information against the equipment drawing and the supplier datasheet:

  • Thread system: PG, metric, NPT, or another specified standard.
  • Thread size and pitch: for example, PG13.5 or M20 × 1.5.
  • Cable outer diameter: measured over the installed jacket.
  • Gland sealing range: minimum and maximum accepted diameter.
  • Gland material: nylon, brass, nickel-plated brass, or stainless steel.
  • Environmental requirement: indoor, outdoor, washdown, dust exposure, or immersion risk.
  • Required IP rating and installation orientation.
  • Locknut, sealing washer, earth tag, and adapter requirements.
  • Temperature range, chemical exposure, vibration, and strain-relief needs.
  • Applicable product and installation certification.

During installation, I keep the gland, locknut, sealing washer, and enclosure face clean. I start the thread by hand to detect resistance early, then tighten according to the manufacturer’s specified method instead of using excessive force. After installation, I check that the cable is centered, the seal is compressed evenly, the gland does not rotate under normal cable movement, and the enclosure entry remains free from visible gaps.

Can a Thread Adapter Convert PG to Metric?

A thread adapter can provide a conversion path, but it is not a universal solution. The adapter must match the original enclosure thread on one side and the replacement gland thread on the other, while also providing adequate engagement, sealing, mechanical strength, and environmental protection.

I use adapters only when the product documentation confirms the dimensional and sealing requirements. The adapter may add length, reduce internal clearance, create a new sealing interface, or affect the enclosure’s IP rating. In hazardous, high-vibration, outdoor, or washdown applications, I require the adapter and gland combination to be approved for the specific installation rather than treating a generic threaded ring as an equivalent replacement.

Conclusion

The key point in PG Thread vs Metric Thread Cable Glands: What's the Difference? is that the two systems differ in thread geometry, pitch, diameter conventions, and application history. Metric glands are generally the better fit for new equipment, while PG glands remain appropriate for older European equipment and retrofit work where the existing enclosure is already threaded for PG.

Before selecting a replacement, I identify the enclosure thread from markings and documentation, measure the gland with calipers, confirm pitch with a thread gauge, and verify the thread profile when necessary. I then match the gland’s cable sealing range to the measured cable outer diameter and confirm material, IP rating, locknut, washer, and certification requirements. This process prevents the common PG13.5-versus-M20 substitution error and produces a more reliable cable-entry installation.